Friction Loss Calculator
When fluids move through a pipe, they rub against the walls and lose energy. That loss shows up as a drop in pressure or as an equivalent “length of water column” called head loss. This page explains friction loss in plain language, shows the right formulas, and walks you through examples so you can use a friction loss calculator with confidence.
What is friction loss?
Picture pushing a heavy box across a concrete floor. The floor resists motion. Pipes behave the same way. Fluid rubs the inner wall and loses energy as heat and turbulence. Engineers measure this as head loss in feet or meters of fluid. You can also express it as pressure loss in psi, bar, Pascal, or pound per square foot.
Head loss rises with flow rate. It falls with a larger inside diameter or with smoother pipe. Long runs add up the loss. Bends, valves, and fittings add extra losses, which you can estimate separately if needed.
How the Friction Loss Calculator works
The calculator converts your inputs to SI units, applies the Hazen–Williams relation, then converts back to the units you choose for display. This approach keeps numerical stability high and avoids rounding drift. It also makes unit changes instant and consistent.
- Inputs: pipe diameter, pipe length, volumetric flow rate, and a Hazen–Williams roughness coefficient C.
- Outputs: friction head loss (ft or m of water) and equivalent pressure loss (psi, bar, Pa, or lb/ft²).
- Assumptions: water or water-like liquids at standard temperatures in pressurized turbulent flow. That’s the intended domain of Hazen–Williams.
Hazen–Williams equation and units
For metric inputs the widely used SI form is:
hf [m] = 10.67 · L [m] · (Q [m³/s])1.852 / ( C1.852 · D [m]4.87 )
Where hf is head loss, L is pipe length, Q is flow, D is inside diameter, and C is the Hazen–Williams roughness coefficient. Higher C means smoother pipe. New plastics often sit near 150. Aged cast iron can drop below 100.
To convert head to pressure, multiply by the weight density of water. Using standard gravity and water density near 20 °C:
P [Pa] = ρ · g · hf P [psi] = (ρ · g · hf) / 6894.757
This simple relationship gives you a clean psi reading so you can match against pump curves or regulator limits.
Typical Hazen–Williams C-values
Pick the closest material and age. If you have field test data, use “Custom” and enter C directly.
| Material | Typical C | Notes |
|---|---|---|
| ABS, PVC, CPVC, PE/HDPE | 150 | Very smooth polymer; new pipe. |
| Aluminum | 140 | Clean, smooth bore. |
| Brass, Copper | 130–140 | Degrades slowly with deposits. |
| Ductile Iron (cement lined) | 140 | Lining keeps C high. |
| Steel, welded & seamless | 140 | New unlined steel around 140. |
| Vitrified Clay | 110 | Common in gravity sewers. |
| Cast Iron (new) | 130 | Unlined; C drops with age. |
| Cast Iron (30–40 years) | 80–90 | Roughness grows with corrosion. |
| Corrugated Metal | 60 | Very rough; expect high loss. |
These values align with standard handbooks used by practitioners. If your system carries slurries, hot liquids, or aggressive chemicals then a field test will always beat a table estimate.
Step-by-step: compute friction loss
- Gather dimensions. Inside diameter matters. If you only know nominal size, look up the real inside diameter for the schedule or wall thickness.
- Convert to consistent units. The calculator handles it for you. If you compute by hand, stick to SI to avoid mixing constants.
- Choose a C-value. Start with a table value, then refine it if you measure performance later.
- Apply Hazen–Williams. Compute hf for the run length of interest. For sections in series, add the head losses.
- Convert to pressure. Decide whether you need head or pressure. Choose ft/m of water or psi/bar for the final report.
Worked examples
Example 1 — Fire main with plastic pipe
Suppose a 6 in HDPE line is 400 ft long and carries 1,200 gpm. What pressure drop should you expect?
- Inside diameter D ≈ 6.065 in = 0.1541 m.
- Length L = 400 ft = 121.92 m.
- Flow Q = 1,200 gpm = 0.0757 m³/s.
- HDPE C ≈ 150.
Plug into the SI Hazen–Williams form:
hf = 10.67 × 121.92 × 0.0757^1.852 / (150^1.852 × 0.1541^4.87)
≈ 6.51 m of water
Convert head to pressure:
P ≈ 998.2 × 9.80665 × 6.51 / 6894.757 ≈ 9.3 psi
A 9–10 psi drop across that run looks reasonable for a smooth six-inch main at this flow.
Example 2 — Old cast iron branch
Now consider a 2 in cast iron branch, 150 ft long, delivering 80 gpm. The pipe is thirty years old. Expect C ≈ 90.
- D ≈ 2.067 in = 0.0525 m.
- L = 150 ft = 45.72 m.
- Q = 80 gpm = 0.00505 m³/s.
hf = 10.67 × 45.72 × 0.00505^1.852 / (90^1.852 × 0.0525^4.87)
≈ 7.65 m
P ≈ 10.9 psi
Smaller, rougher pipe creates a much larger loss for modest flow. That’s why old branches struggle with peak demand.
Common pitfalls and how to avoid them
- Nominal vs inside diameter. The number on the pipe schedule isn’t the hydraulic diameter. Always use the actual bore.
- Wrong C for age. New steel can behave like C=140. Decades later the value can be far lower. Capture condition during design reviews.
- Out of scope fluids. Hazen–Williams suits water at ordinary temperature. For oils, solvents, hot water, or laminar regimes use Darcy–Weisbach with a Moody friction factor instead.
- Ignoring fittings. Bends and valves add “minor” losses that often aren’t minor. Sum equivalent lengths or K-values when estimating a whole line.
- Forgetting elevation. Pumps must overcome elevation gain and friction. Head from grade changes stacks with head from friction.
Choosing sensible units
Pick units that match your drawings and shop practice. Many North American teams default to inches, feet, gallons, and psi. If your source data arrives in metric, keep everything there to avoid conversion slips. Either path works because the calculator converts all inputs to a common system before solving.
| Quantity | US customary | Metric | Identity |
|---|---|---|---|
| Length | 1 ft | 0.3048 m | exact |
| Diameter | 1 in | 25.4 mm | exact |
| Volume | 1 US gal | 3.785411784 L | exact |
| Flow | 1 gpm | 0.0000630902 m³/s | derived |
| Pressure | 1 psi | 6894.757 Pa | exact |
| Head→Pressure | 1 ft of water | 0.4335 psi | @ 4 °C to 20 °C approx. |
Frequently asked questions
Does the calculator include minor losses?
No. It reports straight-run friction loss. To include fittings, either add equivalent lengths for each device or add K-based minor loss pressure to the friction result. Both methods appear in standard design handbooks.
Is Hazen–Williams valid for hot water?
It was derived for water at typical distribution temperatures. As water gets much hotter, viscosity falls and the correlation drifts. For high temperatures or non-water fluids, use Darcy–Weisbach with a temperature-appropriate Reynolds number and friction factor.
Why do my field readings differ?
Real systems gather scale, biofilm, and debris. Flow meters and gauges drift. Valves may not be fully open. Treat table C-values as starting points. If you can, calibrate with a controlled measurement and update your model.
What does a higher C mean?
Higher C means smoother pipe and lower friction. A line with C=150 will show less head loss than the same line with C=100 at the same flow, diameter, and length.
Can I size a pump with friction loss alone?
Use friction loss to define system head. Add static lift, minor losses, and required residual pressure at the endpoint. Then overlay a pump curve to find operating point and efficiency. Never size a pump from friction only.
Further reading
You can dig deeper into pipe hydraulics, minor losses, and friction factors using these trustworthy sources:
- EPANET from the U.S. EPA — free network modeling tool widely used in water distribution design.
- Engineering ToolBox: Hazen–Williams Coefficients — convenient C-value tables with context.
How to use the Friction Loss Calculator on this page
- Select your pipe diameter and unit. If you only know nominal size, check a table for the actual inside diameter.
- Enter the pipe length for the segment you want to analyze.
- Type the flow rate and pick volume/time units. Gallons per minute or cubic feet per second both work.
- Choose a material from the list to load a typical C-value. If you have lab or field data then select “Custom” and type your C.
- Read the friction head loss in feet or meters of water. Switch the unit control to show the number in your preferred head unit.
- Review the pressure loss in psi, bar, Pa, or lb/ft². Toggle units to match your drawings.
Design tips that save headaches later
- Watch velocity. High velocities increase noise and erosion. Many water systems target 3–10 ft/s depending on context.
- Balance pipe size and pump size. A slightly larger pipe may cut friction enough to allow a smaller pump, which often lowers lifetime cost.
- Include growth. If demand may double, check friction at future flow. It’s cheaper to upsize now than rip out later.
Formula summary
| Quantity | Formula | Notes |
|---|---|---|
| Head loss (SI) | hf = 10.67 · L · Q1.852 / (C1.852 · D4.87) | Hazen–Williams, metric form. |
| Pressure from head | P = ρ · g · hf | Water at ~20 °C, g = 9.80665 m/s². |
| Unit change | 1 ft of water ≈ 0.4335 psi | Temperature-dependent; good field estimate. |
When to use Darcy–Weisbach instead
Hazen–Williams is empirical. It shines for cold and tempered water in municipal and building services. If you design for high temperature, for viscous liquids, or for very small diameters and slow velocities then use Darcy–Weisbach. That method determines friction factor from Reynolds number and roughness, which covers a much wider range of fluids and regimes.
A short checklist for your report
- List inside diameter, not nominal size.
- State the C-value and the material age assumption.
- Include the run length, number of fittings, and method used for minor losses.
- Show head loss and pressure loss at the same flow.
- Record the date and person responsible for the estimate.
Glossary
- Head loss: Energy loss expressed as height of fluid that would create the same pressure.
- Pressure drop: Loss expressed directly as pressure units like psi or bar.
- C-value: Hazen–Williams roughness coefficient. Bigger means smoother.
- Minor loss: Loss from fittings, entrances, exits, meters, and valves.
Friction loss determines whether a system delivers enough pressure at the far end. With the Hazen–Williams equation and a reliable friction loss calculator you can check a design in seconds. Pick the correct C-value, enter real inside diameter, and stay honest about flow. You’ll get a head loss and a pressure drop that match what your gauges will see in the field.